Section 6
Current protection
6.1.5
Settings
Table 61:
PHPIOC (50) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Pickup
5 - 2500
Table 62: PHPIOC (50) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.1.6
Monitored data
Table 63: PHPIOC (50) Monitored data
Name
I_A
I_B
I_C
6.1.7
Operation principle
The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block. The
RMS value of each phase current is derived from the fundamental frequency components, as well
as sampled values of each phase current. These phase current values are fed to the instantaneous
phase overcurrent protection function PHPIOC (50). In a comparator the RMS values are compared
to the set operation current value of the function
operation current a signal from the comparator for this phase is set to true. This signal will,
without delay, activate the TRIP signal that is common for all three phases.
PHPIOC (50) can be blocked from the binary input BLOCK.
150
Unit
Step
-
-
%IB
1
Unit
Step
-
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
200
Phase current pickup in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
Unit
Description
A
Current in phase A
A
Current in phase B
A
Current in phase C
Pickup . If a phase current is larger than the set
1MRK 506 326-UUS B
PID-1097-SETTINGS v5
PID-1097-MONITOREDDATA v7
M12913-3 v4