ABB Relion 650 Series Technical Manual page 419

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
13.4.4.4
Settings
Table 369: VMMXU Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
GlobalBaseSel
1 - 6
VLDbRepInt
1 - 300
VLMax
0 - 4000000
VLRepTyp
Cyclic
Dead band
Int deadband
VLAngDbRepInt
1 - 300
Table 370: VMMXU Non group settings (advanced)
Name
Values (Range)
VLZeroDB
0 - 100000
VLHiHilLim
0 - 4000000
VLHiLim
0 - 4000000
VLLowLim
0 - 4000000
VLowLowLim
0 - 4000000
VLMin
0 - 4000000
VLLimHys
0.000 - 100.000
13.4.4.5
Monitored data
Table 371: VMMXU Monitored data
Name
V_AB
VAB_ANGL
V_BC
VBC_ANGL
V_CA
VCA_ANGL
Line distance protection REL650
Technical manual
Unit
Step
-
-
-
1
Type
1
V
1
-
-
Type
1
Unit
Step
m%
1
V
1
V
1
V
1
V
1
V
1
V
0.001
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
1
Selection of one of the Global Base Value
groups
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
170000
Maximum value
Dead band
Reporting type
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Default
Description
500
Zero point clamping
160000
High High limit (physical value)
150000
High limit (physical value)
125000
Low limit (physical value)
115000
Low Low limit (physical value)
0
Minimum value
5.000
Hysteresis value in % of range and is
common for all limits
Unit
Description
kV
V_AB Amplitude
deg
VAB Angle
kV
V_BC Amplitude
deg
VBC Angle
kV
V_CA Amplitude
deg
VCA Angle
Section 13
Monitoring
PID-1231-SETTINGS v5
PID-1231-MONITOREDDATA v7
413

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents