5.3.5
Settings
Table 28: ZMOPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
KNMag1
0.00 - 3.00
KNAng1
-180 - 180
LineAng
-180 - 180
KNMag2
0.00 - 3.00
KNAng2
-180 - 180
IMinPUPG
10 - 30
IMinPUPP
10 - 30
OpModetLG1
Disabled
Enabled
tLG1
0.000 - 60.000
OpModePP1
Disabled
Enabled
tPP1
0.000 - 60.000
Table continues on next page
Line distance protection REL650
Technical manual
ZMOPDIS (21) Output signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
-
Deg
Deg
-
Deg
%IB
%IB
-
s
-
s
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Trip general
Trip zone 1
Trip zone 2
Trip zone 3
Trip zone 4
Trip zone 5
Start general
Zone 1 Pick up
Zone 2 pick up
zone 3 pick up
zone 4 pick up
Zone 5 Pick up
Step
Default
-
Disabled
0.01
0.80
1
-15
1
80
0.01
0.80
1
-15
1
20
1
20
-
Disabled
0.001
0.000
-
Disabled
0.001
0.000
Impedance protection
Description
Operation Disabled/Enabled
Magnitude of ground return compensation
factor KN for zone 1
Angle for ground return compensation
factor KN for zone 1
Line Angle
Magnitude of ground return compensation
factor KN for zones 2,3,4,5
Angle for ground return compensation
factor KN for zones 2,3,4,5
Minimum pickup phase current for Phase-
to-ground loops
Minimum pickup delta current (2 x current
of lagging phase) for Phase-to-phase
loops
Operation mode Off / On of zone timer,
Phase-Ground for zone 1
Time delay to trip of Phase-ground
elements for zone 1
Operation mode Off / On of zone timer,
Phase-Phase for zone 1
Time delay to trip of Phase-Phase
elements for zone 1
Section 5
PID-1479-OUTPUTSIGNALS v7
PID-1479-SETTINGS v7
103