Section 10
Control
The reset timer defines a time from the issue of the reclosing command, after which the reclosing
sequence resets. Should a new trip occur during this time, it is treated as a continuation of the
first fault. The reset timer is started when the CB closing command is given.
A number of outputs for Autoreclosing state control keeps track of the actual state in the
reclosing sequence.
1PT1
3PT1TO
3PT2TO
3PT3TO
3PT4TO
3PT5TO
SYNC
initiate
CBREADY
Pulse STBRREC (79) (above)
TR3P
pickup
initiate
Shot 0
Shot 1
Shot 2
Shot 3
Shot 4
Shot 5
Y
INHIBIT
ANSI10000257 V1 EN-US
Figure 160: Reclosing Reset and Inhibit timers
10.3.6.7
Pulsing of the CB closing command
The duration of the pulse is fixed 200 ms. See figure 161.
When a reclosing command is issued, the appropriate reclosing operation counter is incremented.
There is a counter for each reclosing shot and one for the total number of reclosing commands
issued.
310
OR
AND
AND
AND
LOGIC
reclosing
programs
Blocking
OR
© Copyright 2011 ABB Power Grids. All rights reserved
"STBRREC (79) Open time"
From logic for
t1 3Ph
reclosing
t
programs
AND
AND
tSync
t
tReset
AND
t
OR
Reset Timer On
1PT1
3PT1
OR
3PT2
3PT3
3PT4
3PT5
tInhibit
t
1MRK 506 326-UUS B
timer
3PT1TO
Pulse STBRREC (79)
Blocking
X
OR
STBRREC (79)
State Control
COUNTER
Shot 0
0
CL
Shot 1
1
Shot 2
2
Shot 3
3
Shot 4
R
4
Shot 5
5
INPROGR
Inhibit
Y
ANSI10000257-1-en.vsd
GUID-CAA69161-888C-4A68-BB5C-2C55247AC4CF v1
Line distance protection REL650
Technical manual