ABB Relion 650 Series Technical Manual page 392

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Logic
Name
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
Table 340: B16I Output signals
Name
OUT
12.6.5
Settings
The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)
12.6.6
Monitored data
Table 341: B16I Monitored data
Name
OUT
12.6.7
Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16 binary
inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according to the table below
from 0 to 32768. This follows the general formula: INx = 2
on the activated INx will be available on the output OUT as a sum of the integer values of all the
inputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) are activated, that is =
Boolean 1, it corresponds to that integer 65535 is available on the output OUT. The B16I function is
designed for receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.
386
Type
Default
Description
BOOLEAN
0
Input 4
BOOLEAN
0
Input 5
BOOLEAN
0
Input 6
BOOLEAN
0
Input 7
BOOLEAN
0
Input 8
BOOLEAN
0
Input 9
BOOLEAN
0
Input 10
BOOLEAN
0
Input 11
BOOLEAN
0
Input 12
BOOLEAN
0
Input 13
BOOLEAN
0
Input 14
BOOLEAN
0
Input 15
BOOLEAN
0
Input 16
Type
Description
INTEGER
Output value
Type
Values (Range)
INTEGER
-
© Copyright 2011 ABB Power Grids. All rights reserved
Unit
Description
-
Output value
x-1
where 1≤x≤16. The sum of all the values
Line distance protection REL650
1MRK 506 326-UUS B
PID-1894-OUTPUTSIGNALS v5
ABBD8E241394 v3
PID-1894-MONITOREDDATA v7
SEMOD175737-4 v5
Technical manual