Section 5
Impedance protection
Name
Values (Range)
LdAngle
5 - 70
X0
0.50 - 3000.00
Pickup Iph
10 - 2500
Pickup_N
10 - 2500
X1
0.50 - 3000.00
RFltFwdPP
0.50 - 3000.00
RFltRevPP
0.50 - 3000.00
RFltFwdPG
1.00 - 9000.00
RFltRevPG
1.00 - 9000.00
IMinPUPP
5 - 500
IMinPUPG
5 - 500
Table 23:
FDPSPDIS Group settings (advanced)
Name
Values (Range)
TimerPP
Disabled
Enabled
tPP
0.000 - 60.000
TimerPE
Disabled
Enabled
tPG
0.000 - 60.000
Table 24: FDPSPDIS Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
5.2.6
Operation principle
The basic impedance algorithm for the operation of the phase selection measuring elements is the
same as for the distance zone measuring function. Phase selection with load encroachment,
quadrilateral characteristic FDPSPDIS (21) includes six impedance measuring loops; three intended
for phase-to-ground faults, and three intended for phase-to-phase faults as well as for three-
phase faults.
The difference, compared to the distance zone measuring function, is in the combination of the
measuring quantities (currents and voltages) for different types of faults.
86
Unit
Step
Deg
1
-
0.01
%IB
1
%IB
1
-
0.01
ohm/l
0.01
ohm/l
0.01
ohm/l
0.01
ohm/l
0.01
%IB
1
%IB
1
Unit
Step
-
-
s
0.001
-
-
s
0.001
Unit
Step
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
30
Load angle determining the load
impedance area
120.00
Zero sequence reactance reach
120
Pick up value for phase selection by over-
current element
20
3I0 pickup
40.00
Positive sequence reactance reach
30.00
Fault resistance reach, Phase-Phase,
forward
30.00
Fault resistance reach, Phase-Phase,
reverse
100.00
Fault resistance reach, Phase-Ground,
forward
100.00
Fault resistance reach, Phase-Ground,
reverse
10
Minimum pickup delta current (2 x current
of lagging phase) for Phase-to-phase
loops
5
Minimum pickup phase current for Phase-
to-ground loops
Default
Description
Disabled
Operation mode Off / On of zone timer,
Phase-Phase
3.000
Time delay to trip, Phase-Phase
Disabled
Operation mode Off / On of zone timer,
Phase-Ground
3.000
Time delay to trip, Ground-Earth
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 326-UUS B
M13140-3 v5
Line distance protection REL650
Technical manual