ABB Relion 650 Series Technical Manual page 168

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Current protection
Name
TR_B
TR_C
PICKUP
PU_ST1
PU_ST2
PU_ST3
PU_ST4
PU_A
PU_B
PU_C
6.4.5
Settings
Table 79:
OC4SPTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
Pickup1
5 - 2500
t1
0.000 - 60.000
TD1
0.05 - 999.00
IMin1
1 - 10000
t1Min
0.000 - 60.000
Table continues on next page
162
Type
Description
BOOLEAN
Trip signal from phase B
BOOLEAN
Trip signal from phase C
BOOLEAN
General pickup signal
BOOLEAN
Start signal from step 1
BOOLEAN
Start signal from step 2
BOOLEAN
Start signal from step 3
BOOLEAN
Start signal from step 4
BOOLEAN
Pickup signal from phase A
BOOLEAN
Pickup signal from phase B
BOOLEAN
Pickup signal from phase C
Unit
Step
-
-
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1
s
0.001
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Disable / Enable
Non-directional
Directional mode of step 1 off / non-
directional / forward / reverse
ANSI Def. Time
Selection of time delay curve type for step
1
1000
Phase current operate level for step1 in %
of IBase
0.000
Definite time delay of step 1
0.05
Time multiplier for the inverse time delay
for step 1
100
Minimum operate current for step1in% of
IBase
0.000
Minimum operate time for inverse curves
for step 1
1MRK 506 326-UUS B
PID-2351-SETTINGS v6
Line distance protection REL650
Technical manual