ABB Relion 650 Series Technical Manual page 599

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
19.5
Signal outputs
Table 557: Signal output and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
19.6
Power outputs
Table 558: Power output relays without TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Table 559: Power output relays with TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at V< 48/110/220 V DC
Control voltage range
Current drain through the monitoring circuit
Minimum voltage over the TCS contact
Line distance protection REL650
Technical manual
© Copyright 2011 ABB Power Grids. All rights reserved
Value
250 V AC/DC
5 A
10 A
30 A
≤0.5 A/≤0.1 A/≤0.04 A
Value
250 V AC/DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
Value
250 V DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
20...250 V DC
~1.0 mA
20 V DC
Section 19
Technical data
GUID-CAD6026E-BF75-487E-BA91-CEF705FB65DB v3
GUID-F773051A-F50F-4B12-8CB3-88936A687FDC v4
593