ABB Relion 650 Series Technical Manual page 161

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Table 72:
Name
TRIP
TRST1
TRST2
TRST3
TRST4
PICKUP
PU_ST1
PU_ST2
PU_ST3
PU_ST4
PU_A
PU_B
PU_C
6.3.5
Settings
Table 73:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
Pickup1
5 - 2500
t1
0.000 - 60.000
Table continues on next page
Line distance protection REL650
Technical manual
OC4PTOC (51_67) Output signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
-
-
%IB
s
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Common trip signal
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
Trip signal from step 4
General pickup signal
Start signal from step 1
Start signal from step 2
Start signal from step 3
Start signal from step 4
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Step
Default
-
Disabled
-
Non-directional
-
ANSI Def. Time
1
1000
0.001
0.000
Description
Disable/Enable Operation
Directional mode of step 1 off / non-
directional / forward / reverse
Selection of time delay curve type for step
1
Phase current operate level for step1 in %
of IBase
Definite time delay of step 1
Section 6
Current protection
PID-1800-OUTPUTSIGNALS v5
PID-1800-SETTINGS v5
155