ABB Relion 650 Series Technical Manual page 462

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Monitoring
Analog signals
Binary signals
ANSI09000336 V1 EN-US
Figure 240: Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings, each with the
data coming from all the parts mentioned above. The sequential of events function is working
continuously, independent of disturbance triggering, recording time, and so on. All information in
the disturbance report is stored in non-volatile flash memories. This implies that no information is
lost in case of loss of auxiliary power. Each report will get an identification number in the interval
from 0-999.
Record no. N
General dist.
information
ANSI05000125 V1 EN-US
Figure 241: Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded when the
memory is full, the oldest disturbance report is overwritten by the new one. The total recording
capacity for the disturbance recorder is depending of sampling frequency, number of analog and
binary channels and recording time. In a 60 Hz system it is possible to record 80 where the
maximum recording time is 3.4 seconds. The memory limit does not affect the rest of the
disturbance report (Sequential of events, Event recorder, Indications and Trip value recorder).
456
A1-4RADR
A4RADR
B1-6RBDR
B6RBDR
Disturbance report
Record no. N+1
Trip
Indications
values
recordings
© Copyright 2011 ABB Power Grids. All rights reserved
Disturbance Report
DRPRDRE
Trip value rec
Fault locator
Disturbance
recorder
Sequential of
events
Event recorder
Indications
ANSI09000336-1-en.vsd
Record no. N+100
Event
Disturbance
Fault locator
recording
1MRK 506 326-UUS B
FL
Event list
(SOE)
en05000125_ansi.vsd
Line distance protection REL650
Technical manual