Trip signal issuing requires that the undervoltage condition continues for at least the user set
time delay. This time delay is set by the parameter
some special voltage level dependent time curves for the inverse time mode (TOV). If the pickup
condition, with respect to the measured voltage ceases during the delay time, the corresponding
pickup output is reset.
7.1.7.3
Blocking
It is possible to block Two step undervoltage protection (UV2PTUV ,27) partially or completely, by
binary input signals or by parameter settings, where:
BLOCK:
BLK1:
BLK2:
7.1.7.4
Design
The voltage measuring elements continuously measure the three phase-to-neutral voltages or the
three phase-to-phase voltages. Recursive fourier filters or true RMS filters of input voltage signals
are used. The voltages are individually compared to the set value, and the lowest voltage is used
for the inverse time characteristic integration. A special logic is included to achieve the
out of 3 and 3 out of 3 criteria to fulfill the PICKUP condition. The design of Two step undervoltage
protection UV2PTUV (27) is schematically shown in
Line distance protection REL650
Technical manual
blocks all outputs
blocks all pickup and trip outputs related to step 1
blocks all pickup and trip outputs related to step 2
© Copyright 2011 ABB Power Grids. All rights reserved
t1 and t2 for definite time mode (DT) and by
Figure
122.
Section 7
Voltage protection
M15326-20 v5
M15326-35 v5
1 out of 3 , 2
237