1MRK 506 326-UUS B
13.14.5
Settings
Table 424: SPVNZBAT Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
RtdBattVolt
20.00 - 250.00
BattVoltLowLim
60 - 140
BattVoltHiLim
60 - 140
tDelay
0.000 - 60.000
tReset
0.000 - 60.000
13.14.6
Measured values
Table 425: SPVNZBAT Measured values
Name
U_BATT
BLOCK
13.14.7
Monitored Data
Table 426: SPVNZBAT Monitored data
Name
BATTVOLT
13.14.8
Operation principle
The function can be enabled and disabled with the
parameter values are
The operation of the station battery supervision function can be described by using a module
diagram. All the modules in the diagram are explained in the next sections.
Line distance protection REL650
Technical manual
Unit
Step
-
-
V
1.00
%Vbat
1
%Vbat
1
s
0.001
s
0.001
Type
Default
REAL
0.00
BOOLEAN
0
Type
Values (Range)
REAL
-
Enable and Disable .
The function execution requires that at least one of the function outputs is
connected in configuration.
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Enabled
Disable/Enable Operation
110.00
Battery rated voltage
70
Lower limit for the battery terminal
voltage
120
Upper limit for the battery terminal
voltage
0.200
Delay time for alarm
0.000
Time delay for reset of alarm
Description
Battery terminal voltage that has to be supervised
Blocks all the output signals of the function
Unit
Description
kV
Service value of the battery terminal
voltage
Operation setting. The corresponding
Section 13
Monitoring
PID-2853-SETTINGS v4
PID-2853-MEASUREDVALUES v2
PID-2853-MONITOREDDATA v4
GUID-EA09E2CE-9698-45AF-AB2D-2CBFB1509629 v2
481