Section 5
Impedance protection
Name
Values (Range)
OffsetMhoDir2
Non-directional
Forward
Reverse
BlinderMode2
Disabled
Enabled
LoadEnchMode2
Disabled
Enabled
LoadEnchMode3
Disabled
Enabled
BlinderMode3
Disabled
Enabled
LoadEnchMode4
Disabled
Enabled
BlinderMode4
Disabled
Enabled
LoadEnchMode5
Disabled
Enabled
BlinderMode5
Disabled
Enabled
OffsetMhoDir5
Non-directional
Forward
Reverse
OffsetMhoDir4
Non-directional
Forward
Reverse
OffsetMhoDir3
Non-directional
Forward
Reverse
Table 29: ZMOPDIS (21) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
5.3.6
Operation principle
5.3.6.1
Full scheme measurement
The execution of the different fault loops within the IED are of full scheme type, which means that
each fault loop for phase-to-ground faults and phase-to-phase faults are executed in parallel.
The use of full scheme technique gives faster operation time compared to switched schemes
which mostly uses a phase selector element to select correct voltages and current depending on
fault type. So each distance protection zone performs like one independent distance protection
function with six measuring elements.
106
Unit
Step
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Unit
Step
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Non-directional
Direction mode for offset mho of zone 2
Disabled
Blinder mode Off/On of zone 2
Disabled
Load enchroachment mode Off/On of
zone 2
Disabled
Load enchroachment mode Off/On of
zone 3
Disabled
Blinder mode Off/On of zone 3
Disabled
Load enchroachment mode Off/On of
zone 4
Disabled
Blinder mode Off/On of zone 4
Disabled
Load enchroachment mode Off/On of
zone 5
Disabled
Blinder mode Off/On of zone 5
Non-directional
Direction mode for offset mho of zone 5
Non-directional
Direction mode for offset mho of zone 4
Non-directional
Direction mode for offset mho of zone 3
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 326-UUS B
SEMOD154224-4 v2
Line distance protection REL650
Technical manual