1MRK 506 326-UUS B
13.21.4
Settings
Table 448: I103EF Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
13.22
Function status fault protection for IEC 60870-5-103
I103FLTPROT
13.22.1
Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the function block is
specific for a certain fault type and therefore must be connected to a correspondent signal
present in the configuration. For example: 68_TRGEN represents the General Trip of the device,
and therefore must be connected to the general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is triggering
the Disturbance Recorder and the respective configured signal to the IEC 60870-5-103
I103FLTPROT.
13.22.2
Function block
BLOCK
64_PU_A
65_PU_B
66_PU_C
67_STIN
68_TRGEN
69_TR_A
70_TR_B
71_TR_C
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTR_A
87_MTR_B
88_MTR_C
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
ANSI10000291 V1 EN-US
Figure 268: I103FLTPROT function block
Line distance protection REL650
Technical manual
Unit
-
I103FLTPROT
ANSI10000291-1-en.vsd
© Copyright 2011 ABB Power Grids. All rights reserved
Step
Default
1
160
Description
Function type (1-255)
GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1
GUID-F0ED13B8-6B82-4CA7-8F22-C200C33EBB7E v2
Section 13
Monitoring
PID-2655-SETTINGS v4