ABB Relion 650 Series Technical Manual page 81

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Name
Values (Range)
tPP2
0.000 - 60.000
OpModeLG3
Disabled
Enabled
OpModetPP3
Disabled
Enabled
DirModeSel3
Disabled
Offset
Forward
Reverse
tLG3
0.000 - 60.000
tPP3
0.000 - 60.000
OpModeLG4
Disabled
Enabled
OpModetPP4
Disabled
Enabled
DirModeSel4
Disabled
Offset
Forward
Reverse
tLG4
0.000 - 60.000
tPP4
0.000 - 60.000
OpModeLG5
Disabled
Enabled
OpModetPP5
Disabled
Enabled
DirMode5
Disabled
Offset
Forward
Reverse
tLG5
0.000 - 60.000
tPP5
0.000 - 60.000
OpMode1
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
OpMode2
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
OpMode3
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
OpMode4
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
OpMode5
Disable-Zone
Enable Ph-E
Enable PhPh
Enable Ph-E PhPh
Line distance protection REL650
Technical manual
Unit
Step
s
0.001
-
-
-
-
-
-
s
0.001
s
0.001
-
-
-
-
-
-
s
0.001
s
0.001
-
-
-
-
-
-
s
0.001
s
0.001
-
-
-
-
-
-
-
-
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
0.000
Time delay to trip, Phase-Phase zone 2
Enabled
Operation mode Off / On of zone timer,
Phase-Ground of zone 3
Enabled
Operation mode Off / On of zone timer,
Phase-Phase of zone 3
Forward
Direction mode zone 3
0.000
Time delay to trip, Phase-Ground, zone 3
0.000
Time delay to trip, Phase-Phase zone 3
Enabled
Operation mode Off / On of zone timer,
Phase-Ground of zone 4
Enabled
Operation mode Off / On of zone timer,
Phase-Phase of zone 4
Forward
Direction mode zone 4
0.000
Time delay to trip, Phase-ground, zone 4
0.000
Time delay to trip, Phase-Phase, zone 4
Enabled
Operation mode Off / On of zone timer,
Phase-Ground of zone 5
Enabled
Operation mode Off / On of zone timer,
Phase-Phase of zone 5
Forward
Direction mode zone 5
0.000
Time delay to trip, Phase-ground, zone 5
0.000
Time delay to trip, Phase-Phase, zone 5
Enable Ph-E PhPh
Operation mode of zone 1
Enable Ph-E PhPh
Operation mode of zone 2
Enable Ph-E PhPh
Operation mode of zone 3
Enable Ph-E PhPh
Operation mode of zone 4
Enable Ph-E PhPh
Operation mode of zone 5
Section 5
Impedance protection
75