1MRK 506 326-UUS B
Name
Values (Range)
LevZeroClampQ
0.001 - 10000.000
DirEnergyAct
Forward
Reverse
DirEnergyReac
Forward
Reverse
EAFPrestVal
0.000 -
10000.000
EARPrestVal
0.000 -
10000.000
ERFPresetVal
0.000 -
10000.000
ERRPresetVal
0.000 -
10000.000
14.2.6
Monitored data
Table 466: ETPMMTR Monitored data
Name
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
14.2.7
Operation principle
The instantaneous output values of active and reactive power from the Measurements (CVMMXN)
function block are used and integrated over a selected time
energy. The energy values (in MWh and MVarh) are available as output signals and also as pulsed
output which can be connected to a pulse counter. Outputs are available for forward as well as
reverse direction. The accumulated energy values can be reset from the local HMI reset menu or
with input signal RSTACC.
The maximum demand values for active and reactive power are calculated for the set time
and the maximum value is stored in a register available over communication and from outputs
MAXPAFD, MAXPARD, MAXPRFD, MAXPRRD for the active and reactive power forward and reverse
direction until reset with input signal RSTDMD or from the local HMI reset menu.
Line distance protection REL650
Technical manual
Unit
Step
MVAr
0.001
-
-
-
-
MWh
0.001
MWh
0.001
MVArh
0.001
MVArh
0.001
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
10.000
Zero point clamping level at reactive Power
Forward
Direction of active energy flow Forward/
Reverse
Forward
Direction of reactive energy flow Forward/
Reverse
0.000
Preset Initial value for forward active
energy
0.000
Preset Initial value for reverse active
energy
0.000
Preset Initial value for forward reactive
energy
0.000
Preset Initial value for reverse reactive
energy
Unit
Description
MWh
Accumulated forward active energy value
MWh
Accumulated reverse active energy value
MVArh
Accumulated forward reactive energy
value
MVArh
Accumulated reverse reactive energy value
MW
Maximum forward active power demand
value for set interval
MW
Maximum reverse active power demand
value for set interval
MVAr
Maximum forward reactive power demand
value for set interval
MVAr
Maximum reactive power demand value in
reverse direction
tEnergy to measure the integrated
Section 14
Metering
PID-1869-MONITOREDDATA v8
SEMOD175495-4 v3
tEnergy
517