ABB Relion 650 Series Technical Manual page 342

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
Name
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
10.12.4
Settings
Table 266: I103USRCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
PulseMode
Steady
Pulsed
PulseLength
0.200 - 60.000
InfNo_1
1 - 255
InfNo_2
1 - 255
InfNo_3
1 - 255
InfNo_4
1 - 255
InfNo_5
1 - 255
InfNo_6
1 - 255
InfNo_7
1 - 255
InfNo_8
1 - 255
10.13
Function commands generic for IEC 60870-5-103
I103GENCMD
10.13.1
Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The function has
two outputs signals CMD_OFF and CMD_ON that can be used to implement double-point
command schemes.
10.13.2
Function block
BLOCK
IEC10000285 V1 EN-US
Figure 176: I103GENCMD function block
336
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
-
s
-
-
-
-
-
-
-
-
I103GENCMD
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Command output 5
Command output 6
Command output 7
Command output 8
Step
Default
1
1
-
Pulsed
0.001
0.400
1
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1MRK 506 326-UUS B
Description
Function type (1-255)
Pulse mode
Pulse length
Information number for output 1 (1-255)
Information number for output 2 (1-255)
Information number for output 3 (1-255)
Information number for output 4 (1-255)
Information number for output 5 (1-255)
Information number for output 6 (1-255)
Information number for output 7 (1-255)
Information number for output 8 (1-255)
GUID-729E9AFD-0468-4BBD-B54A-A6CDCC68A9B2 v1
GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1
Line distance protection REL650
Technical manual
PID-2651-SETTINGS v4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents