ABB Relion 650 Series Technical Manual page 520

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 14
Metering
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was updated since last
report.
The SCAL_VAL signal consists of scaled value (according to parameter
information.
14.1.8
Technical data
Table 461: PCGGIO technical data
Function
Cycle time for report of
counter value
14.2
Energy calculation and demand handling ETPMMTR
14.2.1
Identification
Function description
Energy calculation and demand
handling
14.2.2
Functionality
Outputs from the Measurements (CVMMXN) function can be used to calculate energy
consumption. Active as well as reactive values are calculated in import and export direction. Values
can be read or generated as pulses. Maximum demand power values are also calculated by the
function.
514
Setting range
(1–3600) s
IEC 61850
identification
ETPMMTR
© Copyright 2011 ABB Power Grids. All rights reserved
Scale ), time and status
Accuracy
-
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
Wh
IEC10000169 V1 EN-US
Line distance protection REL650
1MRK 506 326-UUS B
M13404-2 v4
SEMOD175537-2 v3
SEMOD153641-8 v5
Technical manual