ABB Relion 650 Series Technical Manual page 203

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
Table 106: LPTTR (26) Input signals
Name
I3P
BLOCK
AMBTEMP
SENSFLT
RESET
Table 107: LPTTR (26) Output signals
Name
TRIP
PICKUP
ALARM
LOCKOUT
TEMP
TEMPAMB
TERMLOAD
6.9.5
Settings
Table 108: LPTTR (26) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
TRef
0 - 600
IRef
0 - 400
Tau
1 - 1000
AlarmTemp
0 - 200
TripTemp
0 - 600
ReclTemp
0 - 600
AmbiSens
Disabled
Enabled
DefaultAmbTemp
-50 - 250
DefaultTemp
-50 - 600
Line distance protection REL650
Technical manual
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
BOOLEAN
0
Block of function
REAL
0
Ambient temperature from external temperature sensor
BOOLEAN
0
Validity status of ambient temperature sensor
BOOLEAN
0
Reset of internal thermal load counter
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
General pickup signal
BOOLEAN
Alarm signal
BOOLEAN
Lockout signal
REAL
Calculated temperature of the device
REAL
Ambient temperature used in the calculations
REAL
Temperature relative to operate temperature
Unit
Step
-
-
Deg
1
%IB
1
Min
1
Deg
1
Deg
1
Deg
1
-
-
Deg
1
Deg
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
90
End temperature rise above ambient of
the line when loaded with IRef
100
Load current in % of IBase leading to TRef
temperature
45
Time constant of the line
80
Temperature level for pickup (alarm)
90
Temperature level for trip
75
Temperature for reset of lockout after trip
Disabled
External temperature sensor available
20
Ambient temperature used when
AmbiSens is set to Off
50
Temperature raise above ambient
temperature at startup
Section 6
Current protection
PID-2593-INPUTSIGNALS v5
PID-2593-OUTPUTSIGNALS v5
PID-2593-SETTINGS v5
197