ABB Relion 650 Series Technical Manual page 391

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
STRNULL is a string, fixed to an empty string (null) value
ZEROSMPL is a channel index, fixed to 0 value
GRP_OFF is a group signal, fixed to 0 value
12.6
Boolean 16 to integer conversion B16I
12.6.1
Identification
Function description
Boolean 16 to integer conversion
12.6.2
Functionality
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16 binary (logical)
signals into an integer.
12.6.3
Function block
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
IEC09000035 V1 EN-US
Figure 217: B16I function block
12.6.4
Signals
Table 339: B16I Input signals
Name
BLOCK
IN1
IN2
IN3
Table continues on next page
Line distance protection REL650
Technical manual
IEC 61850
identification
B16I
OUT
IEC09000035-1-en.vsd
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 60617
identification
B16I
-
Description
Block of function
Input 1
Input 2
Input 3
ANSI/IEEE C37.2
device number
-
PID-1894-INPUTSIGNALS v5
Section 12
Logic
SEMOD175721-2 v2
SEMOD175725-4 v3
SEMOD175798-5 v4
385