Section 13
Monitoring
13.4.6.4
Settings
Table 379: VMSQI Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
3V0DbRepInt
1 - 300
3V0Min
0 - 2000000
3V0Max
0 - 2000000
3V0RepTyp
Cyclic
Dead band
Int deadband
3V0LimHys
0.000 - 100.000
3V0AngDbRepInt
1 - 300
V1DbRepInt
1 - 300
V1Min
0 - 2000000
V1Max
0 - 2000000
V1RepTyp
Cyclic
Dead band
Int deadband
V1AngDbRepInt
1 - 300
V2DbRepInt
1 - 300
V2Min
0 - 2000000
V2Max
0 - 2000000
V2RepTyp
V2LimHys
V2AngDbRepInt
Table 380: VMSQI Non group settings (advanced)
Name
Values (Range)
3V0ZeroDb
0 - 100000
3V0HiHiLim
0 - 2000000
3V0HiLim
0 - 2000000
3V0LowLim
0 - 2000000
3V0LowLowLim
0 - 2000000
Table continues on next page
418
Unit
-
Type
V
V
-
%
Type
Type
V
V
-
Type
Type
V
V
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
%
1 - 300
Type
Unit
m%
V
V
V
V
© Copyright 2011 ABB Power Grids. All rights reserved
Step
Default
-
Disabled
1
10
1
0
1
318000
-
Dead band
0.001
5.000
1
10
1
10
1
0
1
106000
-
Dead band
1
10
1
10
1
0
1
106000
-
Dead band
0.001
5.000
1
10
Step
Default
1
500
1
288000
1
258000
1
213000
1
198000
1MRK 506 326-UUS B
Description
Disable/Enable Operation
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Minimum value
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Description
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)