Section 12
12.1
Tripping logic SMPPTRC (94)
12.1.1
Identification
Function description
Tripping logic
12.1.2
Functionality
A function block for protection tripping is provided for each circuit breaker involved in the tripping
of the fault. It provides pulse prolongation to ensure a trip pulse of sufficient length, as well as all
functionality necessary for correct co-operation with autoreclosing functions.
The trip function block includes functionality for breaker lock-out.
12.1.3
Function block
BLOCK
TRINP_3P
SETLKOUT
RSTLKOUT
ANSI09000284 V1 EN-US
Figure 196: SMPPTRC (94) function block
12.1.4
Signals
Table 297: SMPPTRC (94) Input signals
Name
BLOCK
TRINP_3P
SETLKOUT
RSTLKOUT
Line distance protection REL650
Technical manual
Logic
SMPPTRC (94)
TRIP
CLLKOUT
ANSI09000284-1-en.vsd
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
SMPPTRC
I->O
SYMBOL-K V1 EN-US
Default
Description
0
Block of function
0
Trip all phases
0
Input for setting the circuit breaker lockout function
0
Input for resetting the circuit breaker lockout function
GUID-B56D86A1-47D9-4B45-A90B-B622C3AE5D2D v1
ANSI/IEEE C37.2
device number
94
PID-1133-INPUTSIGNALS v9
Section 12
Logic
SEMOD56226-2 v3
M12275-3 v5
M12638-3 v5
361