ABB Relion 650 Series Technical Manual page 274

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 9
Secondary system supervision
9.1.4
Signals
Table 202: CCSRDIF (87) Input signals
Name
I3P
IREF
BLOCK
Table 203: CCSRDIF (87) Output signals
Name
FAIL
ALARM
9.1.5
Settings
Table 204: CCSRDIF (87) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IMinOp
5 - 200
Table 205: CCSRDIF (87) Group settings (advanced)
Name
Values (Range)
Pickup_Block
5 - 500
Table 206: CCSRDIF (87) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
9.1.6
Operation principle
Current circuit supervision CCSRDIF (87) compares the absolute value of the vectorial sum of the
three phase currents |ΣIphase| and the numerical value of the residual current |Iref| from another
current transformer set, see figure 137.
268
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
GROUP
-
Group signal for current reference
SIGNAL
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Detection of current circuit failure
BOOLEAN
Alarm for current circuit failure
Unit
Step
-
-
%IB
1
Unit
Step
%IB
1
Unit
Step
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
20
Minimum operate current differential
pickup in % of IBase
Default
Description
150
Block of the function at high phase
current, in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 326-UUS B
PID-1124-INPUTSIGNALS v5
PID-1124-OUTPUTSIGNALS v5
PID-1124-SETTINGS v5
M12396-5 v4
Line distance protection REL650
Technical manual