ABB Relion 650 Series Technical Manual page 505

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
GUID-A913D2D7-398B-41F6-9B21-BBCECD3F596D V1 EN-US
Figure 262: Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals LOPRES and ALMPRES.
Pressure alarm time delay
When the ALMPRES binary input is activated, the PRESALM alarm is activated after a time delay set
with the
If the pressure drops further to a very low level, the LOPRES binary input becomes high, activating
the lockout alarm PRESLO after a time delay set with the
be blocked by activating the BLOCK input.
The binary input BLOCK can be used to block the function. The activation of the BLOCK input
deactivates all outputs and resets internal timers. The alarm signals from the function can be
blocked by activating the binary input BLK_ALM.
13.17.8
Technical data
Table 440: SSCBR Technical data
Function
Alarm levels for open and close
travel time
Alarm levels for number of
operations
Setting of alarm for spring charging
time
Time delay for gas pressure alarm
Time delay for gas pressure lockout
13.18
Measurands for IEC 60870-5-103 I103MEAS
13.18.1
Functionality
103MEAS is a function block that reports all valid measuring types depending on connected
signals.
Line distance protection REL650
Technical manual
tPressAlm setting. The PRESALM alarm can be blocked by activating the BLOCK input.
© Copyright 2011 ABB Power Grids. All rights reserved
TPressLO setting. The PRESLO alarm can
Range or value
(0-200) ms
(0 - 9999)
(0.00-60.00) s
(0.00-60.00) s
(0.00-60.00) s
Monitoring
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v2
Accuracy
± 0.5% ± 25 ms
-
± 0.5% ± 25 ms
± 0.5% ± 25 ms
± 0.5% ± 25 ms
GUID-557FB587-9127-4D99-B2C6-16445E06F220 v1
Section 13
499