Section 12
Logic
Table 298: SMPPTRC (94) Output signals
Name
TRIP
CLLKOUT
12.1.5
Settings
Table 299: SMPPTRC (94) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tTripMin
0.000 - 60.000
Table 300: SMPPTRC (94) Group settings (advanced)
Name
Values (Range)
TripLockout
Disabled
Enabled
AutoLock
Disabled
Enabled
12.1.6
Operation principle
The duration of a trip output signal from tripping logic SMPPTRC (94) is settable (
pulse length should be long enough to secure the breaker opening.
For three-pole tripping, SMPPTRC (94) has a single input (TRINP_3P) through which all trip output
signals from the protection functions within the IED, or from external protection functions via one
or more of the IEDs binary inputs, are routed. It has a single trip output (TRIP) for connection to
one or more of the IEDs binary outputs, as well as to other functions within the IED requiring this
signal.
ANSI05000789 V2 EN-US
Figure 197: Simplified logic diagram for three pole trip
In multi-breaker arrangements, one SMPPTRC (94) function block is used for each breaker.
362
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Circuit breaker lockout output (set until reset)
Unit
Step
-
-
s
0.001
Unit
Step
-
-
-
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Enabled
Disable/Enable Operation
0.150
Minimum duration of trip output signal
Default
Description
Disabled
On: Activate output (CLLKOUT) and trip
latch, Off: Only output
Disabled
On: Lockout from input (SETLKOUT) and
trip, Off: Only input
1MRK 506 326-UUS B
PID-1133-OUTPUTSIGNALS v9
PID-1133-SETTINGS v9
M12255-3 v6
tTripMin ). The
Line distance protection REL650
Technical manual