ABB Relion 650 Series Technical Manual page 321

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
10.4.2
Bay control QCBAY
10.4.2.1
Identification
Function description
Bay control
10.4.2.2
Functionality
The Bay control QCBAY function is used together with Local remote and local remote control
functions to handle the selection of the operator place per bay. QCBAY also provides blocking
functions that can be distributed to different apparatuses within the bay.
10.4.2.3
Function block
QCBAY
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
IEC09000080_1_en.vsd
IEC09000080 V1 EN-US
Figure 165: QCBAY function block
10.4.2.4
Signals
Table 234: QCBAY Input signals
Name
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
Table 235: QCBAY Output signals
Name
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
Line distance protection REL650
Technical manual
IEC 61850
identification
QCBAY
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Type
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 60617
identification
-
Description
External Local/Remote switch is in Off position
External Local/Remote switch is in Local position
External Local/Remote switch is in Remote position
Data representing the L/R switch position is valid
Steady signal to block the position updates
Steady signal to block the command
Description
Value for the operator place allocation
Update of position is blocked
Function is blocked for commands
Local operation allowed
Remote operation allowed
GUID-0D5EE38C-0DEB-4753-AF0B-72286C4A98DA v1
ANSI/IEEE C37.2
device number
-
PID-1959-INPUTSIGNALS v5
PID-1959-OUTPUTSIGNALS v5
Section 10
Control
M13447-3 v5
M13469-3 v4
315