ABB Relion 650 Series Technical Manual page 80

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 5
Impedance protection
Name
Values (Range)
RFPP4
1.00 - 3000.00
RFPP5
1.00 - 3000.00
Z1
0.005 - 3000.000
Z2
0.005 - 3000.000
Z3
0.005 - 3000.000
Z4
0.005 - 3000.000
Z5
0.005 - 3000.000
IMinPUPP
10 - 30
IMinPUPG
10 - 30
IMinOpIR
5 - 30
LineAng
0 - 180
KNMag1
0.00 - 3.00
KNMag2
0.00 - 3.00
KNAng1
KNAng2
OpModetLG1
OpModePP1
DirModeSel1
tLG1
tPP1
OpModeLG2
OpModetPP2
DirModeSel2
tLG2
Table continues on next page
74
Unit
ohm/l
ohm/l
-
-
-
-
-
%IB
%IB
%IB
Deg
-
-
-180 - 180
Deg
-180 - 180
Deg
Disabled
-
Enabled
Disabled
-
Enabled
Disabled
-
Offset
Forward
Reverse
0.000 - 60.000
s
0.000 - 60.000
s
Disabled
-
Enabled
Disabled
-
Enabled
Disabled
-
Offset
Forward
Reverse
0.000 - 60.000
s
© Copyright 2011 ABB Power Grids. All rights reserved
Step
Default
0.01
30.00
0.01
30.00
0.001
30
0.001
30
0.001
30
0.001
30
0.001
30
1
20
1
20
1
5
1
80
0.01
0.80
0.01
0.80
1
0
1
0
-
Enabled
-
Enabled
-
Forward
0.001
0.000
0.001
0.000
-
Enabled
-
Enabled
-
Forward
0.001
0.000
1MRK 506 326-UUS B
Description
Fault resistance reach, Phase-Phase, zone
4
Fault resistance reach, Phase-Phase, zone
5
Positive sequence impedance reach for
zone 1
Positive sequence impedance reach for
zone 2
Positive sequence impedance reach for
zone 3
Positive sequence impedance reach for
zone 4
Positive sequence impedance reach for
zone 5
Minimum pickup delta current (2 x current
of lagging phase) for Phase-to-phase
loops
Minimum pickup phase current for Phase-
to-ground loops
Minimum operate residual current for
Phase-Ground loops
Line angle for zone 1, 2, 3, 4 and 5
Magnitude of ground return compensation
factor KN for zone 1
Magnitude of earth return compensation
factor KN for zone 2, 3, 4 and 5
Angle for ground return compensation
factor KN for zone 1
Angle for ground return compensation
factor for zone 2, 3, 4 and 5
Operation mode Off / On of zone timer,
Phase-Ground of zone 1
Operation mode Off / On of zone timer,
Phase-Phase of zone 1
Direction mode zone 1
Time delay to trip, Ground-Earth, zone 1
Time delay to trip, Phase-Phase, zone 1
Operation mode Off / On of zone timer,
Phase-Ground of zone 2
Operation mode Off / On of zone timer,
Phase-Phase of zone 2
Direction mode zone 2
Time delay to trip, Phase-Ground, zone 2
Line distance protection REL650
Technical manual