1MRK 506 326-UUS B
The parameter
between.
ANSIC09000063 V1 EN-US
Figure 289: Connection of the function to external circuits
The above example also includes five output signals, for confirmation of which group that is
active.
16.5
Test mode functionality TESTMODE
16.5.1
Identification
Function description
Test mode functionality
16.5.2
Functionality
When the Test mode functionality TESTMODE function is activated, protection functions in the IED
are automatically blocked. It is then possible to unblock the protection functions individually from
the local HMI or the Parameter Setting tool to perform required tests.
When leaving TESTMODE, all blockings are removed and the IED resumes normal operation.
However, if during TESTMODE operation, power is removed and later restored, the IED will remain
in TESTMODE with the same protection functions blocked or unblocked as before the power was
removed. All testing will be done with actually set and configured values within the IED. No
settings will be changed, thus mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.
Line distance protection REL650
Technical manual
MaxNoSetGrp defines the maximum number of setting groups in use to switch
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1
Æ
IOx-Bly2
Æ
IOx-Bly3
Æ
IOx-Bly4
Æ
IEC 61850
identification
TESTMODE
© Copyright 2011 ABB Power Grids. All rights reserved
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
GRP4
ACTGRP4
GRP_CHGD
ANSI09000063_1_en.vsd
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 16
Basic IED functions
GUID-0411129B-3A42-4A3B-A8E7-178D0EA5A7EA v2
M4803-3 v6
553