Section 5
Impedance protection
5.5.4
Signals
Table 37:
Name
I3P
V3P
Table 38: ZDNRDIR (21D) Output signals
Name
DIR_POL
STDIRCND
5.5.5
Settings
Table 39: ZDNRDIR (21D) Group settings (basic)
Name
Values (Range)
AngNegRes
90 - 175
AngDir
5 - 45
IMinPUPG
5 - 30
IMinPUPP
5 - 30
Table 40: ZDNRDIR (21D) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
130
ZDNRDIR (21D) Input signals
Type
Default
GROUP
SIGNAL
GROUP
SIGNAL
Type
GROUP SIGNAL
INTEGER
Unit
Deg
Deg
%IB
%IB
Unit
-
© Copyright 2011 ABB Power Grids. All rights reserved
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
Description
Polarizing voltage output for Mho
Binary coded directional information per measuring loop
Step
Default
1
115
1
15
1
5
1
10
Step
Default
1
1
1MRK 506 326-UUS B
Description
Angle of blinder in second quadrant for
forward direction
Angle of blinder in fourth quadrant for
forward direction
Minimum pickup phase current for Phase-
to-ground loops
Minimum pickup delta current (2 x current
of lagging phase) for Phase-to-phase
loops
Description
Selection of one of the Global Base Value
groups
Line distance protection REL650
Technical manual
PID-1615-INPUTSIGNALS v6
PID-1615-OUTPUTSIGNALS v6
PID-1615-SETTINGS v6