Table 283: ZCLCPLAL Output signals
Name
TRZE
TRLL
11.3.5
Settings
Table 284: ZCLCPLAL Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
LoadCurr
1 - 100
LossOfLoad
Disabled
Enabled
ZoneExtension
Disabled
Enabled
MinCurr
1 - 100
tLowCurr
0.000 - 60.000
tLoadOn
0.000 - 60.000
tLoadOff
0.000 - 60.000
Table 285: ZCLCPLAL Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
11.3.6
Operation principle
11.3.6.1
Zone extension
The overreaching zone is connected to the input EXACC. For this reason, configure the ARREADY
functional input to a READY functional output of a used autoreclosing function or via the selected
binary input to an external autoreclosing device, see figure 187.
This will allow the overreaching zone to trip instantaneously.
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Trip by zone extension
BOOLEAN
Trip by loss of load
Unit
Step
-
-
%IB
1
-
-
-
-
%IB
1
s
0.001
s
0.001
s
0.001
Unit
Step
-
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
10
Load current before disturbance in % of
IBase
Disabled
Enable/Disable operation of Loss of load
Disabled
Enable/Disable operation of Zone
extension
5
Level taken as current loss due to remote
CB trip in % of IBase
0.200
Time delay on pick-up for MINCURR value
0.000
Time delay on pick-up for load current
release
0.300
Time delay on drop off for load current
release
Default
Description
1
Selection of one of the Global Base Value
groups
Section 11
Scheme communication
PID-1519-OUTPUTSIGNALS v5
PID-1519-SETTINGS v5
M13819-3 v2