1MRK 506 326-UUS B
ANSI05000287 V1 EN-US
Figure 113: Pole discrepancy external detection logic
This binary signal is connected to a binary input of the IED. The appearance of this signal will start
a timer that will give a trip signal after the set time delay.
Pole discrepancy can also be detected by means of phase selective current measurement. The
sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block. From the
fundamental frequency components of each phase current the RMS value of each phase current is
derived. The smallest and the largest phase current are derived. If the smallest phase current is
lower than the setting
is started. The
long. The current based pole discrepancy function can be set to be active either continuously or
only directly in connection to breaker open or close command.
EXTPDIND
CLOSECMD
OPENCMD
ANSI08000014 V1 EN-US
Figure 114: Simplified block diagram of pole discrepancy function - contact and current
The pole discordance protection is blocked if the input signal BLOCK is high.
Line distance protection REL650
Technical manual
C.B.
52a
52a
52a
52b
52b
52b
CurrUnsymPU times the largest phase current the settable trip timer ( tTrip )
tTrip timer gives a trip signal after the set delay. The TRIP signal is a pulse 150 ms
ContactSel
AND
tTrip+200 ms
OR
AND
CurrentSel
Unsymmetrical
current detection
based
© Copyright 2011 ABB Power Grids. All rights reserved
+
poleDiscrepancy Signal from C.B.
AND
OR
ANSI_en05000287.vsd
tTrip
150 ms
TRIP
t
ANSI08000014-1-en.vsd
Section 6
Current protection
M13946-3 v5
215