Section 13
Monitoring
The measurand reporting interval set for MMXU function blocks, using the
xAngDbRepInt settings, must be coordinated with the event reporting interval set for the IEC
60870-5-103 communication using setting
GUID-B8A3A04C-430D-4488-9F72-8529FAB0B17D V1 EN-US
Figure 263: Settings for CMMXU: 1
All input signals to IEC 60870-5-103 I103MEAS must be connected in application configuration.
Connect an input signals on IEC 60870-5-103 I103MEAS that is not connected to the corresponding
output on MMXU function, to outputs on the fixed signal function block.
13.18.2
Function block
BLOCK
I_A
I_B
I_C
IN
V_A
V_B
V_C
V_AB
V_N
P
Q
F
ANSI10000287 V1 EN-US
Figure 264: I103MEAS function block
500
I103MEAS
ANSI10000287-1-en.vsd
© Copyright 2011 ABB Power Grids. All rights reserved
CycMeasRepTime .
1MRK 506 326-UUS B
xDbRepInt and
GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v1
Line distance protection REL650
Technical manual