1MRK 506 326-UUS B
5.8.5
Settings
Table 56: ZCVPSOF Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Mode
Impedance
VILevel
VILvl&Imp
AutoInit
Disabled
Enabled
IphPickup
1 - 100
UVPickup
1 - 100
tDuration
0.000 - 60.000
tSOTF
0.000 - 60.000
tDLD
0.000 - 60.000
Table 57:
ZCVPSOF Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
5.8.6
Operation principle
Automatic switch onto fault logic, voltage and current based function (ZCVPSOF) can be activated
externally by Breaker Closed Input or internally (automatically) by using VI Level Based Logic see
figure 83.
The activation from the Dead line detection function is released if the internal signal deadLine
from the VILevel function is activated at the same time as the input ZACC is not activated during
at least for a duration
When the setting
get a trip one of the following operation modes must also be selected by the parameter
Mode = Impedance ; trip is released if the input ZACC is activated (normal connected to non
directional distance protection zone).
Mode = VILevel ; trip is released if VILevel detector is activated.
Mode = VILvl&Imp ; trip is initiated based on impedance measured criteria or VILevel detection.
The internal signal deadLine from the VILevel detector is activated if all three phase currents and
voltages are below the setting
Line distance protection REL650
Technical manual
Unit
Step
-
-
-
-
-
-
%IB
1
%VB
1
s
0.001
s
0.001
s
0.001
Unit
Step
-
1
tDLD and the setting parameter AutoInit is set to Enabled .
AutoInit is Disabled , the function is activated by an external binary input BC. To
IPhPickup and UVPickup .
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Enabled
Operation Disable / Enable
VILevel
Mode of operation of SOTF Function
Disabled
Automatic switch onto fault initialization
20
Current level for detection of dead line in
% of IBase
70
Voltage level for detection of dead line in
% of VBase
0.020
Time delay for UI detection
1.000
Drop off delay time of switch onto fault
function
0.200
Delay time for activation of dead line
detection
Default
Description
1
Selection of one of the Global Base Value
groups
Section 5
Impedance protection
PID-1521-SETTINGS v5
SEMOD153665-4 v4
Mode :
147