ABB Relion 650 Series Technical Manual page 522

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 14
Metering
Name
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
14.2.5
Settings
Table 464: ETPMMTR Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
StartAcc
Disabled
Enabled
tEnergy
1 Minute
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls
0.000 - 60.000
tEnergyOffPls
0.000 - 60.000
EAFAccPlsQty
0.001 - 10000.000
EARAccPlsQty
0.001 - 10000.000
ERFAccPlsQty
0.001 - 10000.000
ERRAccPlsQty
0.001 - 10000.000
Table 465: ETPMMTR Non group settings (advanced)
Name
Values (Range)
EALim
0.001 -
10000000000.00
0
ERLim
0.001 -
10000000000.00
0
EnZeroClamp
Disabled
Enabled
LevZeroClampP
0.001 - 10000.000
Table continues on next page
516
Type
Description
REAL
Accumulated forward reactive energy value
REAL
Accumulated reverse reactive energy value
REAL
Maximum forward active power demand value for set interval
REAL
Maximum reverse active power demand value for set interval
REAL
Maximum forward reactive power demand value for set interval
REAL
Maximum reactive power demand value in reverse direction
Unit
Step
-
-
-
-
-
-
s
0.001
s
0.001
MWh
0.001
MWh
0.001
MVArh
0.001
MVArh
0.001
Unit
Step
MWh
0.001
MVArh
0.001
-
-
MW
0.001
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Enable/Disable
Disabled
Activate the accumulation of energy values
1 Minute
Time interval for energy calculation
1.000
Energy accumulated pulse ON time
0.500
Energy accumulated pulse OFF time
100.000
Pulse quantity for active forward
accumulated energy value
100.000
Pulse quantity for active reverse
accumulated energy value
100.000
Pulse quantity for reactive forward
accumulated energy value
100.000
Pulse quantity for reactive reverse
accumulated energy value
Default
Description
1000000.000
Active energy limit
1000.000
Reactive energy limit
Enabled
Enable of zero point clamping detection
function
10.000
Zero point clamping level at active Power
1MRK 506 326-UUS B
PID-1869-SETTINGS v5
Line distance protection REL650
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents