1MRK 506 326-UUS B
15.5.5
Settings
Table 479: GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
15.5.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
15.6
GOOSE function block to receive an integer value
GOOSEINTRCV
15.6.1
Identification
Function description
GOOSE function block to receive an
integer value
15.6.2
Functionality
GOOSEINTRCV is used to receive an integer value from the sender using IEC61850 protocol over
GOOSE.
Line distance protection REL650
Technical manual
Unit
Step
-
-
The input of this GOOSE block must be crossed in the SMT to receive the double
point values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
IEC 61850
identification
GOOSEINTRCV
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operation Enable/Disable
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 15
Station communication
PID-2528-SETTINGS v6
GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v1
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v1