1MRK 506 326-UUS B
Table 278: ZCWSPSCH (85) Output signals
Name
IRVL
TRWEI
TRWEI_A
TRWEI_B
TRWEI_C
ECHO
11.2.5
Settings
Table 279: ZCWSPSCH (85) Group settings (basic)
Name
Values (Range)
CurrRev
Disabled
Enabled
tPickUpRev
0.000 - 60.000
tDelayRev
0.000 - 60.000
WEI
Disabled
Echo
Echo & Trip
tPickUpWEI
0.000 - 60.000
PU27PP
10 - 90
PU27PN
10 - 90
Table 280: ZCWSPSCH (85) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
11.2.6
Operation principle
11.2.6.1
Current reversal logic
The current reversal logic uses a reverse zone connected to the input IREV to recognize the fault on
the parallel or any other outgoing line in any of the phases. When the reverse zone has been
activated for a certain settable time
and activation of trip signal for a predefined time
signal to reset before the trip signal is activated due to the current reversal by the forward
directed zone, see figure 183.
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Operation of current reversal logic
BOOLEAN
Trip of WEI logic
BOOLEAN
Trip of WEI logic in phase A
BOOLEAN
Trip of WEI logic in phase B
BOOLEAN
Trip of WEI logic in phase C
BOOLEAN
A signal that indicates channel start (CS) by WEI logic
Unit
Step
-
-
s
0.001
s
0.001
-
-
s
0.001
%VB
1
%VB
1
Unit
Step
-
1
tPickUpRev it prevents sending of a communication signal
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Operating mode of Current Reversal Logic
0.020
Pickup time for current reversal logic
0.060
Time Delay to prevent Carrier send and
local trip
Disabled
Operating mode of WEI logic
0.010
Coordination time for the WEI logic
70
Phase to Phase voltage for detection of
fault condition
70
Phase to Neutral voltage for detection of
fault condition
Default
Description
1
Selection of one of the Global Base Value
groups
tDelayRev . This makes it possible for the receive
Section 11
Scheme communication
PID-2348-OUTPUTSIGNALS v7
PID-2348-SETTINGS v7
GUID-E378B492-0874-4C8A-BDEC-59DE4284FEC1 v1
345