1MRK 506 326-UUS B
8.3.4
Signals
Table 198: SAPFRC (81) Input signals
Name
V3P
BLOCK
Table 199: SAPFRC (81) Output signals
Name
TRIP
PICKUP
RESTORE
BLKDMAGN
8.3.5
Settings
Table 200: SAPFRC (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFreqGrad
-10.00 - 10.00
tTrip
0.000 - 60.000
RestoreFreq
45.00 - 65.00
tRestore
0.000 - 60.000
8.3.6
Operation principle
Rate-of-change frequency protection SAPFRC (81) is used to detect fast power system frequency
changes, increase as well as, decrease at an early stage. SAPFRC (81) has a settable definite time
delay. If the rate-of-change of frequency remains below the set value, for negative rate-of-change,
for a time period equal to the chosen time delay, the TRIP signal is issued. If the rate-of-change of
frequency remains above the set value, for positive rate-of-change, for a time period equal to the
chosen time delay, the TRIP signal is issued. To avoid an unwanted trip due to uncertain frequency
measurement at low voltage magnitude, a voltage controlled blocking of the function is available
from the preprocessing function that is, if the voltage is lower than the set blocking voltage in the
preprocessing function, the function is blocked and no PICKUP or TRIP signal is issued. If the
frequency recovers, after a frequency decrease, a restore signal is issued.
Line distance protection REL650
Technical manual
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Operate/trip signal for frequency gradient
BOOLEAN
Start/pick-up signal for frequency gradient
BOOLEAN
Restore signal for load restoring purposes
BOOLEAN
Blocking indication due to low magnitude
Unit
Step
-
-
Hz/s
0.01
s
0.001
Hz
0.01
s
0.001
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
0.50
Frequency gradient pick up value, the sign
defines direction
0.200
Operate time delay in positive / negative
frequency gradient mode
49.90
Restore is enabled if frequency is above
set frequency value
0.000
Restore time delay
Section 8
Frequency protection
PID-1962-INPUTSIGNALS v6
PID-1962-OUTPUTSIGNALS v6
PID-1962-SETTINGS v6
M14970-3 v4