Section 13
Monitoring
Name
Values (Range)
MV hLim
-5000.00 -
5000.00
MV lLim
-5000.00 -
5000.00
MV llLim
-5000.00 -
5000.00
MV min
-5000.00 -
5000.00
MV max
-5000.00 -
5000.00
MV dbType
Cyclic
Dead band
Int deadband
MV limHys
0.000 - 100.000
13.3.6
Monitored data
Table 356: MVGGIO Monitored data
Name
VALUE
RANGE
13.3.7
Operation principle
Upon receiving an analog signal at its input, IEC61850 generic communication I/O functions
(MVGGIO) will give the instantaneous value of the signal and the range, as output values. In the
same time, it will send over IEC 61850-8-1 the value, to other IEC 61850 clients in the substation.
13.4
Measurements
13.4.1
Functionality
Measurement functions is used for power system measurement, supervision and reporting to the
local HMI, monitoring tool within PCM600 or to station level for example, via IEC 61850. The
possibility to continuously monitor measured values of active power, reactive power, currents,
voltages, frequency, power factor etc. is vital for efficient production, transmission and
distribution of electrical energy. It provides to the system operator fast and easy overview of the
present status of the power system. Additionally, it can be used during testing and commissioning
of protection and control IEDs in order to verify proper operation and connection of instrument
transformers (CTs and VTs). During normal service by periodic comparison of the measured value
from the IED with other independent meters the proper operation of the IED analog measurement
402
Unit
Step
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
-
-
%
0.001
Type
Values (Range)
REAL
-
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
800.00
High limit multiplied with the base prefix
(multiplication factor)
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
-900.00
Low Low limit multiplied with the base
prefix (multiplication factor)
-1000.00
Minimum value multiplied with the base
prefix (multiplication factor)
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
Dead band
Reporting type
5.000
Hysteresis value in % of range (common
for all limits)
Unit
Description
-
Magnitude of deadband value
-
Range
1MRK 506 326-UUS B
PID-2851-MONITOREDDATA v4
SEMOD55936-5 v5
SEMOD54488-4 v7
Line distance protection REL650
Technical manual