ABB Relion 650 Series Technical Manual page 228

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Current protection
Name
Values (Range)
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
Table 147: GOPPDOP (32) Group settings (advanced)
Name
Values (Range)
k
0.00 - 0.99
Table 148: GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
6.15.2.5
Monitored data
Table 149: GOPPDOP (32) Monitored data
Name
P
PPERCENT
Q
QPERCENT
6.15.3
Directional underpower protection GUPPDUP (37)
222
Unit
Step
%
0.1
Deg
0.1
s
0.001
Unit
Step
-
0.01
Unit
Step
-
1
-
-
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
1.0
Power setting for stage 2 in % of
calculated power base value
0.0
Characteristic angle for stage 2
1.000
Trip delay for stage 2
Default
Description
0.00
Low pass filter coefficient for power
measurement, V and I
Default
Description
1
Selection of one of the Global Base Value
groups
Pos Seq
Mode of measurement for current and
voltage
Unit
Description
MW
Active Power
%
Active power in % of calculated power
base value
MVAr
Reactive power
%
Reactive power in % of calculated power
base value
1MRK 506 326-UUS B
PID-2725-MONITOREDDATA v5
SEMOD156693-1 v4
Line distance protection REL650
Technical manual