The first criterion means that detection of failure in one phase together with high current for the
same phase will set the output. The measured phase current is used to reduce the risk of false
fuse failure detection. If the current on the protected line is low, a voltage drop in the system (not
caused by fuse failure) is not by certain followed by current change and a false fuse failure might
occur.
The second criterion requires that the delta condition shall be fulfilled in any phase at the same
time as circuit breaker is closed. Opening circuit breaker at one end and energizing the line from
other end onto a fault could lead to wrong start of the fuse failure function at the end with the
open breaker. If this is considering to be an important disadvantage, connect the 52a input to
FALSE. In this way only the first criterion can activate the delta function.
Line distance protection REL650
Technical manual