ABB Relion 650 Series Technical Manual page 180

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 6
Current protection
Name
Values (Range)
IMin4
1 - 10000
t4Min
0.000 - 60.000
HarmRestrain4
Disabled
Enabled
Table 92: EF4PTOC (51N_67N) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.6.6
Monitored data
Table 93: EF4PTOC (51N_67N) Monitored data
Name
IOp
VPol
IPol
VPolIang
IPOLIANG
6.6.7
Operation principle
This function has the following three "Analog Inputs" on its function block in the configuration
tool:
1.
I3P, input used for "Operating Quantity".
2.
V3P, input used for "Voltage Polarizing Quantity".
3.
I3PPOL, input used for "Current Polarizing Quantity".
These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.
6.6.7.1
Operating quantity within the function
The function always uses Residual Current (3I
be:
1.
directly measured (when a dedicated CT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block connected to EF4PTOC (51N/67N) function
input I3P). This dedicated IED CT input can be for example, connected to:
174
Unit
Step
%IB
1
s
0.001
-
-
Unit
Step
-
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
17
Minimum operate current for step 4 in %
of IBase
0.000
Minimum operate time in inverse curves
step 4
Enabled
Enable block of step 4 from harmonic
restrain
Default
Description
1
Selection of one of the Global Base Value
groups
Unit
Description
A
Operating current level
kV
Polarizing voltage level
A
Polarizing current level
deg
Angle between polarizing voltage and
operating current
deg
Angle between polarizing current and
operating current
) for its operating quantity. The residual current can
0
1MRK 506 326-UUS B
PID-1798-MONITOREDDATA v6
M13941-51 v2
M13941-58 v4
Line distance protection REL650
Technical manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650

Table of Contents