ABB Relion 650 Series Technical Manual page 566

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 16
Basic IED functions
16.10.2.2
Function block
BLOCK
DFTSPFC
REVROT
^GRP1_A
^GRP1_B
^GRP1_C
^GRP1_N
ANSI09000137 V1 EN-US
Figure 292: SMAI_20_1 function block
16.10.2.3
Signals
Table 514: SMAI_20_1 Input signals
Name
BLOCK
DFTSPFC
REVROT
GRP1_A
GRP1_B
GRP1_C
GRP1_N
Table 515: SMAI_20_1 Output signals
Name
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
560
SMAI_20_1
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
ANSI09000137-1-en.vsd
Type
Default
BOOLEAN
0
REAL
20.0
BOOLEAN
0
STRING
-
STRING
-
STRING
-
STRING
-
Type
REAL
GROUP SIGNAL
GROUP SIGNAL
GROUP SIGNAL
GROUP SIGNAL
GROUP SIGNAL
GROUP SIGNAL
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Block group 1
Number of samples per fundamental cycle used for DFT
calculation
Reverse rotation group 1
First analog input used for phase L1 or L1-L2 quantity
Second analog input used for phase B or BC quantity
Third analog input used for phase C or CA quantity
Fourth analog input used for residual or neutral quantity
Description
Number of samples per fundamental cycle from internal DFT
reference function
Grouped three phase signal containing data from inputs 1-4
Quantity connected to the first analog input
Quantity connected to the second analog input
Quantity connected to the third analog input
Quantity connected to the fourth analog input
Calculated residual quantity if inputs 1-3 are connected
1MRK 506 326-UUS B
SEMOD55766-1 v2
SEMOD54868-4 v5
PID-1251-INPUTSIGNALS v11
PID-1251-OUTPUTSIGNALS v9
Line distance protection REL650
Technical manual