1MRK 506 326-UUS B
6.12.4
Signals
Table 126: STBPTOC (50STB) Input signals
Name
I3P
BLOCK
ENABLE
Table 127: STBPTOC (50STB) Output signals
Name
TRIP
PICKUP
6.12.5
Settings
Table 128: STBPTOC (50STB) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IPickup
1 - 2500
Table 129: STBPTOC (50STB) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.12.6
Monitored data
Table 130: STBPTOC (50STB) Monitored data
Name
I_A
I_B
I_C
Line distance protection REL650
Technical manual
Type
Default
Description
GROUP
-
Three phase group signal for current inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Enable stub protection usually with open disconnect switch (89b)
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
General pickup signal
Unit
Step
-
-
%IB
1
Unit
Step
-
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
200
Pickup current level in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
Unit
Description
A
Current in phase A
A
Current in phase B
A
Current in phase C
Section 6
Current protection
PID-1131-INPUTSIGNALS v5
PID-1131-OUTPUTSIGNALS v5