1MRK 506 326-UUS B
parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point,
send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining
parameters will be regarded were appropriate. ex: pulse-On, on-time=100, off-time=300, count=5
would give 5 positive 100 ms pulses, 300 ms apart.
There is a BLOCK input signal, which will disable the operation of the function, in the same way the
Operation : Enabled/Disabled does. That means that, upon activation of the BLOCK input,
setting
all 32 CMDBITxx outputs will be set to 0. The BLOCK acts like an overriding, the function still
receives data from the DNP3 master. Upon deactivation of BLOCK, all the 32 CMDBITxx outputs
will be set by the DNP3 master again, momentarily. For AUTOBITS , the PSTO input determines the
operator place. The command can be written to the block while in "Remote". If PSTO is in "Local"
then no change is applied to the outputs.
For description of the DNP3 protocol implementation, refer to DNP3 communication protocol
manual.
10.10
Function commands for IEC 60870-5-103 I103CMD
10.10.1
Functionality
I103CMD is a command function block in control direction with pre-defined output signals.
10.10.2
Function block
BLOCK
IEC10000282 V1 EN-US
Figure 173: I103CMD function block
10.10.3
Signals
Table 258: I103CMD Input signals
Name
BLOCK
Table 259: I103CMD Output signals
Name
16-AR
17-DIFF
18-PROT
Line distance protection REL650
Technical manual
I103CMD
16-AR
17-DIFF
18-PROT
IEC10000282-1-en.vsd
Type
Default
BOOLEAN
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Block of commands
Description
Information number 16, block of autorecloser
Information number 17, block of differential protection
Information number 18, block of protection
Section 10
Control
GUID-973929FE-292B-42A5-ACF9-BC95E2B16AE1 v1