Section 12
Logic
Function block
INPUT1
INPUT2
INPUT3
INPUT4
IEC09000289 V1 EN-US
Figure 213: AND function block
Signals
Table 327: AND Input signals
Name
INPUT1
INPUT2
INPUT3
INPUT4
Table 328: AND Output signals
Name
OUT
NOUT
Settings
The function does not have any parameters available in Local HMI or Protection and Control IED
Manager (PCM600).
12.4.1.10
Set-reset memory function block SRMEMORY
Identification
Function description
Set-reset memory function block
Functionality
The Set-Reset function SRMEMORY is a flip-flop with memory that can set or reset an output from
two inputs respectively. Each SRMEMORY function block has two outputs, where one is inverted.
The memory setting controls if the flip-flop after a power interruption will return the state it had
before or if it will be reset. For a Set-Reset flip-flop, SET input has higher priority over RESET input.
380
AND
OUT
NOUT
IEC09000289-1-en.vsd
Type
Default
BOOLEAN
1
BOOLEAN
1
BOOLEAN
1
BOOLEAN
1
Type
BOOLEAN
BOOLEAN
IEC 61850
identification
SRMEMORY
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Input signal 1
Input signal 2
Input signal 3
Input signal 4
Description
Output signal
Inverted output signal
IEC 60617
identification
-
1MRK 506 326-UUS B
GUID-E2A77ADC-F947-4041-AA41-1402070A0889 v2
PID-1400-INPUTSIGNALS v7
PID-1400-OUTPUTSIGNALS v7
GUID-50A2CEA0-2781-4C5F-B184-F09FC666876F v1
GUID-4659B1A1-B14C-4A8C-AB72-869949A6DAA0 v1
ANSI/IEEE C37.2
device number
-
GUID-C36DC217-8B3F-4217-A0F9-A3F6B0127CF9 v1
Line distance protection REL650
Technical manual