1MRK 506 326-UUS B
13.6.2.2
Function block
IEC09000346 V1 EN-US
Figure 236: DRPRDRE function block
13.6.2.3
Signals
Table 393: DRPRDRE Output signals
Name
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
13.6.2.4
Settings
Table 394: DRPRDRE Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PreFaultRecT
0.05 - 3.00
PostFaultRecT
0.1 - 10.0
TimeLimit
0.5 - 8.0
PostRetrig
Disabled
Enabled
MaxNoStoreRec
10 - 100
ZeroAngleRef
1 - 30
OpModeTest
Disabled
Enabled
Line distance protection REL650
Technical manual
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
s
s
s
-
-
Ch
-
© Copyright 2011 ABB Power Grids. All rights reserved
Description
Disturbance report function turned off
Disturbance recording started
Disturbance recording made
All disturbances in the disturbance report cleared
More than 80% of memory used
Step
Default
-
Disabled
0.01
0.10
0.1
0.5
0.1
1.0
-
Disabled
1
100
1
1
-
Disabled
GUID-C23997FE-C6FA-473B-A0E7-3E8E980D2213 v2
Description
Operation Enable/Disable
Pre-fault recording time
Post-fault recording time
Fault recording time limit
Post-fault retrig enabled (On) or not (Off)
Maximum number of stored disturbances
Trip value recorder, phasor reference
channel
Operation mode during test mode
Section 13
Monitoring
PID-1248-OUTPUTSIGNALS v5
PID-1248-SETTINGS v6
435