1MRK 506 326-UUS B
Table 416: LMBRFLO Output signals
Name
CALCMADE
FLTDISTX
BCD_80
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
13.13.5
Settings
Table 417: LMBRFLO Group settings (basic)
Name
Values (Range)
R1A
0.001 - 1500.000
X1A
0.001 - 1500.000
R1B
0.001 - 1500.000
X1B
0.001 - 1500.000
R1L
0.001 - 1500.000
X1L
0.001 - 1500.000
R0L
0.001 - 1500.000
X0L
0.001 - 1500.000
R0M
0.000 - 1500.000
X0M
0.000 - 1500.000
LineLength
0.0 - 10000.0
Table 418: LMBRFLO Non group settings (basic)
Name
Values (Range)
DrepChNoI_A
1 - 30
DrepChNoI_B
1 - 30
DrepChNoI_C
1 - 30
DrepChNoIN
0 - 30
Table continues on next page
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Fault calculation made
REAL
Reactive distance to fault
BOOLEAN
Distance in binary coded data, bit represents 80%
BOOLEAN
Distance in binary coded data, bit represents 40%
BOOLEAN
Distance in binary coded data, bit represents 20%
BOOLEAN
Distance in binary coded data, bit represents 10%
BOOLEAN
Distance in binary coded data, bit represents 8%
BOOLEAN
Distance in binary coded data, bit represents 4%
BOOLEAN
Distance in binary coded data, bit represents 2%
BOOLEAN
Distance in binary coded data, bit represents 1%
Unit
Step
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
-
0.1
Unit
Step
Ch
1
Ch
1
Ch
1
Ch
1
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
2.000
Source resistance A (near end)
12.000
Source reactance A (near end)
2.000
Source resistance B (far end)
12.000
Source reactance B (far end)
2.000
Positive sequence line resistance
12.500
Positive sequence line reactance
8.750
Zero sequence line resistance
50.000
Zero sequence line reactance
0.000
Zero sequence mutual resistance
0.000
Zero sequence mutual reactance
40.0
Length of line
Default
Description
1
Recorder Input number recording phase
current, IA
2
Recorder Input number recording phase
current, IB
3
Recorder Input number recording phase
current, IC
4
Recorder input number recording residual
current, IN
Section 13
Monitoring
PID-1797-OUTPUTSIGNALS v5
IP14083-1 v2
PID-1797-SETTINGS v5
473