Section 6
Current protection
6.15
Directional over-/under-power protection GOPPDOP/
GUPPDUP (32/37)
6.15.1
Functionality
The directional over-/under-power protection GOPPDOP (32)/GUPPDUP (37) can be used wherever
a high/low active, reactive or apparent power protection or alarming is required. The functions
can alternatively be used to check the direction of active or reactive power flow in the power
system. There are a number of applications where such functionality is needed. Some of them are:
detection of reversed active power flow
detection of high reactive power flow
Each function has two steps with definite time delay. Reset times for both steps can be set as well.
6.15.2
Directional overpower protection GOPPDOP (32)
6.15.2.1
Identification
Function description
Directional overpower protection
6.15.2.2
Function block
I3P*
V3P*
BLOCK
BLK1
BLK2
ANSI08000506 V1 EN-US
Figure 117: GOPPDOP (32) function block
220
GOPPDOP (32)
TRIP
TRIP1
TRIP2
BFI_3P
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI08000506-1-en.vsd
© Copyright 2011 ABB Power Grids. All rights reserved
IEC 61850
IEC 60617
identification
identification
GOPPDOP
P >
DOCUMENT172362-IMG158942
V1 EN-US
1MRK 506 326-UUS B
GUID-1CC8CF0E-5283-472D-AC4D-46CFD031D458 v1
ANSI/IEEE C37.2
device number
32
Line distance protection REL650
Technical manual
SEMOD175421-4 v5
SEMOD172360-1 v4
SEMOD176574-2 v4
SEMOD172667-4 v4