Name
TR1P
TR3P
CLLKOUT
12.2.5
Settings
Table 304: SPTPTRC (94) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Program
3 phase
1p/3p
tTripMin
0.000 - 60.000
Table 305: SPTPTRC (94) Group settings (advanced)
Name
Values (Range)
TripLockout
Disabled
Enabled
AutoLock
Disabled
Enabled
12.2.6
Operation principle
The duration of a trip output signal from tripping logic SPTPTRC (94) function is settable
tTripMin ). The pulse length should be long enough to secure the breaker opening.
(
For three-pole tripping, SPTPTRC (94) function has a single input (TRIN) through which all trip
output signals from the protection functions within the IED, or from external protection functions
via one or more of the IEDs binary inputs, are routed. It has a single trip output (TRIP) for
connection to one or more of the IEDs binary outputs, as well as to other functions within the IED
requiring this signal. See figure 199.
BLOCK
TRIN
Operation Mode = Enabled
Program = 3 phase
ANSI10000266 V1 EN-US
Figure 199: Simplified logic diagram for three pole trip
Line distance protection REL650
Technical manual
Type
Description
BOOLEAN
Tripping single-pole
BOOLEAN
Tripping three-pole
BOOLEAN
Circuit breaker lockout output (set until reset)
Unit
Step
-
-
-
-
s
0.001
Unit
Step
-
-
-
-
AND
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Enabled
Disable/Enable Operation
3 phase
Three phase / single or three phase
0.150
Minimum duration of trip output signal
Default
Description
Disabled
On: Activate output (CLLKOUT) and trip
latch, Off: Only output
Disabled
On: Lockout from input (SETLKOUT) and
trip, Off: Only input
tTripMin
OR
t
ANSI10000266-1-en.vsd
Section 12
Logic
PID-2344-SETTINGS v5
GUID-0E70E5F5-8B4B-4DBB-B018-D50DFCAA35B3 v2
TRIP
365