ABB Relion 650 Series Technical Manual page 253

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 506 326-UUS B
7.3.4
Signals
Table 176: ROV2PTOV (59N) Input signals
Name
V3P
BLOCK
BLK1
BLK2
Table 177: ROV2PTOV (59N) Output signals
Name
TRIP
TRST1
TRST2
PICKUP
PU_ST1
PU_ST2
7.3.5
Settings
Table 178: ROV2PTOV (59N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Pickup1
1 - 200
t1
0.00 - 6000.00
t1Min
0.000 - 60.000
TD1
0.05 - 1.10
Table continues on next page
Line distance protection REL650
Technical manual
Type
Default
Description
GROUP
-
Three phase group signal for voltage inputs
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of step 1
BOOLEAN
0
Block of step 2
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Trip signal from step 1
BOOLEAN
Trip signal from step 2
BOOLEAN
General pickup signal
BOOLEAN
Start signal from step 1
BOOLEAN
Start signal from step 2
Unit
Step
-
-
-
-
-
-
%VB
1
s
0.01
s
0.001
-
0.01
© Copyright 2011 ABB Power Grids. All rights reserved
Default
Description
Disabled
Disable/Enable Operation
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step
1
30
Voltage start value (DT & IDMT) in % of
VBase for step 1
5.00
Definite time delay of step 1
5.000
Minimum operate time for inverse curves
for step 1
0.05
Time multiplier for the inverse time delay
for step 1
Section 7
Voltage protection
PID-2718-INPUTSIGNALS v5
PID-2718-OUTPUTSIGNALS v5
PID-2718-SETTINGS v5
247